A43 Modbus register map

Core read-only instrumentation block from the official A43 Modbus mapping. Register addresses are the hexadecimal protocol offsets stated by ABB.

MAP OVERVIEW

2 groups, 26 decoded points.

01Voltage and current10 tags02Power16 tags
REGISTER MAP

Searchable source data.

Documentation addresses are derived from the zero-based PDU address in the public definition. Convert a documentation address to its PDU offset when comparing with the manual. Confirm the map against revision 2CMC484001M0201 Rev E and the installed device before commissioning.

Voltage and current

10 of 10
Signal / registerDoc addressPDUTypeUnitNotes
Phase voltage L1-N440994098–4099uint32VRead-only ABB DMTME-compatible instrumentation value.
Phase voltage L2-N441014100–4101uint32VRead-only ABB DMTME-compatible instrumentation value.
Phase voltage L3-N441034102–4103uint32VRead-only ABB DMTME-compatible instrumentation value.
Line voltage L1-L2441054104–4105uint32VRead-only ABB DMTME-compatible instrumentation value.
Line voltage L2-L3441074106–4107uint32VRead-only ABB DMTME-compatible instrumentation value.
Line voltage L1-L3441094108–4109uint32VRead-only ABB DMTME-compatible instrumentation value.
Line current L1441134112–4113uint32ARead-only ABB DMTME-compatible instrumentation value.
Line current L2441154114–4115uint32ARead-only ABB DMTME-compatible instrumentation value.
Line current L3441174116–4117uint32ARead-only ABB DMTME-compatible instrumentation value.
Frequency441674166–4167uint32HzRead-only ABB DMTME-compatible instrumentation value.

Power

16 of 16
Signal / registerDoc addressPDUTypeUnitNotes
System power factor441194118–4119int32—Read-only ABB DMTME-compatible instrumentation value.
Power factor L1441214120–4121int32—Read-only ABB DMTME-compatible instrumentation value.
Power factor L2441234122–4123int32—Read-only ABB DMTME-compatible instrumentation value.
Power factor L3441254124–4125int32—Read-only ABB DMTME-compatible instrumentation value.
System apparent power441354134–4135uint32VARead-only ABB DMTME-compatible instrumentation value.
Apparent power L1441374136–4137uint32VARead-only ABB DMTME-compatible instrumentation value.
Apparent power L2441394138–4139uint32VARead-only ABB DMTME-compatible instrumentation value.
Apparent power L3441414140–4141uint32VARead-only ABB DMTME-compatible instrumentation value.
System active power441434142–4143uint32WRead-only ABB DMTME-compatible instrumentation value.
Active power L1441454144–4145uint32WRead-only ABB DMTME-compatible instrumentation value.
Active power L2441474146–4147uint32WRead-only ABB DMTME-compatible instrumentation value.
Active power L3441494148–4149uint32WRead-only ABB DMTME-compatible instrumentation value.
System reactive power441514150–4151uint32VArRead-only ABB DMTME-compatible instrumentation value.
Reactive power L1441534152–4153uint32VArRead-only ABB DMTME-compatible instrumentation value.
Reactive power L2441554154–4155uint32VArRead-only ABB DMTME-compatible instrumentation value.
Reactive power L3441574156–4157uint32VArRead-only ABB DMTME-compatible instrumentation value.
SOURCE & SCOPE

Import the map, then verify the device.

The catalogue provides register metadata, not a connection profile. Serial port, Unit ID, baud rate and site-specific naming stay in your Busloom project.