SDM72CT-M Modbus register map

Conservative core measurement subset transcribed from the official SDM72CT-M Modbus documentation.

MAP OVERVIEW

2 groups, 21 decoded points.

01Live electrical values19 tags02Energy2 tags
REGISTER MAP

Searchable source data.

Documentation addresses are derived from the zero-based PDU address in the public definition. Convert a documentation address to its PDU offset when comparing with the manual. Confirm the map against revision 2023 protocol and the installed device before commissioning.

Live electrical values

19 of 19
Signal / registerDoc addressPDUTypeUnitNotes
Phase 1 voltage300010–1float32VRead-only IEEE 754 measurement from the official FC04 input-register map.
Phase 2 voltage300032–3float32VRead-only IEEE 754 measurement from the official FC04 input-register map.
Phase 3 voltage300054–5float32VRead-only IEEE 754 measurement from the official FC04 input-register map.
Phase 1 current300076–7float32ARead-only IEEE 754 measurement from the official FC04 input-register map.
Phase 2 current300098–9float32ARead-only IEEE 754 measurement from the official FC04 input-register map.
Phase 3 current3001110–11float32ARead-only IEEE 754 measurement from the official FC04 input-register map.
Phase 1 active power3001312–13float32WRead-only IEEE 754 measurement from the official FC04 input-register map.
Phase 2 active power3001514–15float32WRead-only IEEE 754 measurement from the official FC04 input-register map.
Phase 3 active power3001716–17float32WRead-only IEEE 754 measurement from the official FC04 input-register map.
Phase 1 power factor3003130–31float32—Read-only IEEE 754 measurement from the official FC04 input-register map.
Phase 2 power factor3003332–33float32—Read-only IEEE 754 measurement from the official FC04 input-register map.
Phase 3 power factor3003534–35float32—Read-only IEEE 754 measurement from the official FC04 input-register map.
Average line-neutral voltage3004342–43float32VRead-only IEEE 754 measurement from the official FC04 input-register map.
Average current3004746–47float32ARead-only IEEE 754 measurement from the official FC04 input-register map.
Total active power3005352–53float32WRead-only IEEE 754 measurement from the official FC04 input-register map.
Total apparent power3005756–57float32VARead-only IEEE 754 measurement from the official FC04 input-register map.
Total reactive power3006160–61float32VArRead-only IEEE 754 measurement from the official FC04 input-register map.
Total power factor3006362–63float32—Read-only IEEE 754 measurement from the official FC04 input-register map.
Frequency3007170–71float32HzRead-only IEEE 754 measurement from the official FC04 input-register map.

Energy

2 of 2
Signal / registerDoc addressPDUTypeUnitNotes
Import active energy3007372–73float32kWhRead-only IEEE 754 measurement from the official FC04 input-register map.
Export active energy3007574–75float32kWhRead-only IEEE 754 measurement from the official FC04 input-register map.
SOURCE & SCOPE

Import the map, then verify the device.

The catalogue provides register metadata, not a connection profile. Serial port, Unit ID, baud rate and site-specific naming stay in your Busloom project.