EASTRON · PUBLIC DEVICE MAP

SDM230-Modbus register map

Official core FC04 measurement map for the Eastron SDM230-Modbus single-phase meter, based on protocol revision V1.1. Values are 32-bit IEEE 754 floats in normal register order.

MAP OVERVIEW

3 groups, 20 decoded points.

01Live electrical values8 tags02Energy4 tags03Demand8 tags
REGISTER MAP

Searchable source data.

Documentation addresses are derived from the zero-based PDU address in the public definition. Convert a documentation address to its PDU offset when comparing with the manual. Confirm the map against revision V1.1 and the installed device before commissioning.

Live electrical values

8 of 8
Signal / registerDoc addressPDUTypeUnitNotes
Line-to-neutral voltage300010–1float32VPhase 1 line-to-neutral voltage.
Current300076–7float32APhase 1 current.
Active power3001312–13float32WPhase 1 active power.
Apparent power3001918–19float32VAPhase 1 apparent power.
Reactive power3002524–25float32VArPhase 1 reactive power.
Power factor3003130–31float32—Phase 1 power factor.
Phase angle3003736–37float32°Phase 1 phase angle.
Frequency3007170–71float32HzSupply frequency.

Energy

4 of 4
Signal / registerDoc addressPDUTypeUnitNotes
Import active energy3007372–73float32kWhImported active energy since the last reset.
Export active energy3007574–75float32kWhExported active energy since the last reset.
Import reactive energy3007776–77float32kVArhImported reactive energy since the last reset.
Export reactive energy3007978–79float32kVArhExported reactive energy since the last reset.

Demand

8 of 8
Signal / registerDoc addressPDUTypeUnitNotes
Active power demand3008584–85float32WCurrent active power demand.
Maximum active power demand3008786–87float32WMaximum active power demand.
Forward active power demand3008988–89float32WCurrent forward active power demand.
Maximum forward active power demand3009190–91float32WMaximum forward active power demand.
Reverse active power demand3009392–93float32WCurrent reverse active power demand.
Maximum reverse active power demand3009594–95float32WMaximum reverse active power demand.
Current demand30259258–259float32ACurrent current-demand value.
Maximum current demand30265264–265float32AMaximum current-demand value.
SOURCE & SCOPE

Import the map, then verify the device.

The catalogue provides register metadata, not a connection profile. Serial port, Unit ID, baud rate and site-specific naming stay in your Busloom project.