SDM120-Modbus register map

Official core FC04 measurement map for the Eastron SDM120-Modbus single-phase meter, based on protocol revision V2.4. Values are 32-bit IEEE 754 floats in normal register order.

MAP OVERVIEW

3 groups, 21 decoded points.

01Live electrical values7 tags02Energy6 tags03Demand8 tags
REGISTER MAP

Searchable source data.

Documentation addresses are derived from the zero-based PDU address in the public definition. Convert a documentation address to its PDU offset when comparing with the manual. Confirm the map against revision V2.4 and the installed device before commissioning.

Live electrical values

7 of 7
Signal / registerDoc addressPDUTypeUnitNotes
Voltage300010–1float32VLine voltage.
Current300076–7float32ALine current.
Active power3001312–13float32WInstantaneous active power.
Apparent power3001918–19float32VAInstantaneous apparent power.
Reactive power3002524–25float32VArInstantaneous reactive power.
Power factor3003130–31float32—Signed power factor.
Frequency3007170–71float32HzSupply frequency.

Energy

6 of 6
Signal / registerDoc addressPDUTypeUnitNotes
Import active energy3007372–73float32kWhImported active energy.
Export active energy3007574–75float32kWhExported active energy.
Import reactive energy3007776–77float32kVArhImported reactive energy.
Export reactive energy3007978–79float32kVArhExported reactive energy.
Total active energy30343342–343float32kWhTotal active energy according to the configured measurement mode.
Total reactive energy30345344–345float32kVArhTotal reactive energy.

Demand

8 of 8
Signal / registerDoc addressPDUTypeUnitNotes
Total system power demand3008584–85float32WCurrent total active power demand.
Maximum total system power demand3008786–87float32WMaximum total active power demand.
Import power demand3008988–89float32WCurrent imported active power demand.
Maximum import power demand3009190–91float32WMaximum imported active power demand.
Export power demand3009392–93float32WCurrent exported active power demand.
Maximum export power demand3009594–95float32WMaximum exported active power demand.
Current demand30259258–259float32ACurrent line-current demand.
Maximum current demand30265264–265float32AMaximum line-current demand.
SOURCE & SCOPE

Import the map, then verify the device.

The catalogue provides register metadata, not a connection profile. Serial port, Unit ID, baud rate and site-specific naming stay in your Busloom project.