SIEMENS · PUBLIC DEVICE MAP

SENTRON PAC3200 Modbus register map

Official core measurement map for the Siemens SENTRON PAC3200. The manual permits FC03 and FC04 for these offsets; this definition uses FC03 holding-register views and 32-bit IEEE 754 floats in most-significant-word-first order.

MAP OVERVIEW

4 groups, 29 decoded points.

01Voltage & frequency7 tags02Current3 tags03Power & power factor16 tags04Power quality3 tags
REGISTER MAP

Searchable source data.

Documentation addresses are derived from the zero-based PDU address in the public definition. Convert a documentation address to its PDU offset when comparing with the manual. Confirm the map against revision A5E01168664B-04 and the installed device before commissioning.

Voltage & frequency

7 of 7
Signal / registerDoc addressPDUTypeUnitNotes
Voltage Va-n400021–2float32VManual register offset 1.
Voltage Vb-n400043–4float32VManual register offset 3.
Voltage Vc-n400065–6float32VManual register offset 5.
Voltage Va-b400087–8float32VManual register offset 7.
Voltage Vb-c400109–10float32VManual register offset 9.
Voltage Vc-a4001211–12float32VManual register offset 11.
Frequency4005655–56float32HzManual register offset 55.

Current

3 of 3
Signal / registerDoc addressPDUTypeUnitNotes
Current a4001413–14float32AManual register offset 13.
Current b4001615–16float32AManual register offset 15.
Current c4001817–18float32AManual register offset 17.

Power & power factor

16 of 16
Signal / registerDoc addressPDUTypeUnitNotes
Apparent power a4002019–20float32VAManual register offset 19.
Apparent power b4002221–22float32VAManual register offset 21.
Apparent power c4002423–24float32VAManual register offset 23.
Active power a4002625–26float32WManual register offset 25.
Active power b4002827–28float32WManual register offset 27.
Active power c4003029–30float32WManual register offset 29.
Reactive power a4003231–32float32varManual register offset 31.
Reactive power b4003433–34float32varManual register offset 33.
Reactive power c4003635–36float32varManual register offset 35.
Power factor a4003837–38float32—Manual register offset 37.
Power factor b4004039–40float32—Manual register offset 39.
Power factor c4004241–42float32—Manual register offset 41.
Total apparent power4006463–64float32VAManual register offset 63.
Total active power4006665–66float32WManual register offset 65.
Total reactive power4006867–68float32varManual register offset 67.
Total power factor4007069–70float32—Manual register offset 69.

Power quality

3 of 3
Signal / registerDoc addressPDUTypeUnitNotes
Voltage THD-R a4004443–44float32%Voltage total harmonic distortion, phase a.
Voltage THD-R b4004645–46float32%Voltage total harmonic distortion, phase b.
Voltage THD-R c4004847–48float32%Voltage total harmonic distortion, phase c.